The KL4132 analog output terminal generates signals in the range from -10 to +10 V. The voltage is supplied to the process level with a resolution of 16 bits and is electrically isolated. The output channels of a Bus Terminal have a common ground potential. The two run LEDs give an indication of the data exchange with the Bus Coupler.
| Technical data | KL4132 | KS4132 |
|---|---|
| Technology | single-ended |
| Number of outputs | 2 |
| Power supply | via the K-bus |
| Signal voltage | -10…+10 V |
| Load | > 5 kΩ (short-circuit-proof) |
| Output error | < ±0.1 % (relative to end value) |
| Resolution | 16 bits |
| Conversion time | ~ 1.5 ms |
| Electrical isolation | 500 V (K-bus/signal voltage) |
| Current consumption power contacts | – (no power contacts) |
| Current consumpt. K-bus | typ. 75 mA |
| Bit width in the process image | output: 2 x 16 bit data (2 x 8 bit control/status optional) |
| Configuration | no address or configuration setting |
| Special features | increased resolution |
| Weight | approx. 85 g |
| Operating/storage temperature | 0…+55 °C/-25…+85 °C |
| Relative humidity | 95 %, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27/29 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. class/installation pos. | IP 20/variable |
| Pluggable wiring | for all KSxxxx Bus Terminals |
| Approvals | CE, UL, Ex |
![]() |
![]() |
| Special terminals | |
|---|---|
| KL4132-0010 | Siemens S5 format |
| KL4132-0050 | Siemens S7 format |
![]() |
![]() |