3-phase power measurement terminal up to 690 V AC EL3413
L3 OK, L3 Error
L2 OK, L2 Error
L1 OK, L1 Error
ccw/cw
IL3 OK, IL3 Error 
IL2 OK, IL2 Error 
IL1 OK, IL1 Error 
Run LED 
Current
measurement IL1
Current
measurement IL2
Current
measurement IL3
L1
L2
L3
N
Top view 
Contact assembly 

EL3413 | 3-phase power measurement terminal up to 690 V AC

The EL3413 EtherCAT power measurement terminal is a further development of the EL3403. With up to 690 V AC the voltage inputs are optimised for direct monitoring of high-performance generators, as used in the wind power industry, for example. No upstream voltage transformer is required. The current inputs are galvanically isolated so that the terminal can be used in all common grounded current transformer configurations such as 2- or 3-transformer configurations with star or delta connection. The EL3413 can deal with simple network analysis up to the 21st harmonic analysis. Like all measured terminal data, the harmonic content can be read via the process data.

Technical data EL3413
Number of inputs 3 x current, 3 x voltage
Technology 3-phase power measurement for alternating voltages
Oversampling factor
Distributed clocks
Conversion time mains-synchronous
Measured values current, voltage, effective power, reactive power, apparent power, energy, cos φ, frequency, harmonic oscillation
Measuring voltage max. 690 V AC 3~ (ULX-N: max. 400 V AC)
Measuring current adjustable, 100 mA, 1 A (default), 5 A; potential-free
Resolution 1 μA, 0.1 mV, 10 mW
Measuring error 0.5 % relative to full scale value (U/I), 1 % calculated value
Electrical isolation 4,500 V
Current consumption power contacts
Current consumption E-bus typ. 160 mA
Special features galvanically isolated current inputs, harmonic analysis, single-phase operation also possible
Weight approx. 100 g
Operating/storage temperature 0…+55 °C/-25…+85 °C
Relative humidity 95 %, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos. IP 20/variable