The EL6224 IO-Link terminal enables connection of up to four IO-Link devices, e.g. actuators, sensors or combinations of both. A point-to-point connection is used between the terminal and the device. The terminal is parameterised via the EtherCAT master. IO-Link is designed as an intelligent link between the fieldbus level and the sensor, wherein parameterisation information can be exchanged bidirectionally via the IO-Link connection. The parameterisation of the IO-Link devices with service data can be done from TwinCAT via ADS.
In the standard setting, the EL6224 functions as a 4-channel input terminal, 24 V DC, which communicates with connected IO-Link devices, parameterises them and, if necessary, changes their operating mode.
So far, the EL6224 has been manufactured in the standard housing with eight connection points. Integration into the HD housing with 16 connection points now enables each IO-Link device to be operated in 2-wire connection mode (so-called physics 1) or 3-wire connection mode (so-called physics 2). The direct plug-in technique enables toolless construction.
| Technical data | EL6224 |
|---|---|
| Technology | IO-Link input/output |
| IO-Link interfaces | 4 |
| Field voltage | 24 V DC via power contacts |
| Connection | physics 1 (2-wire) or physics 2 (3-wire) |
| Data transfer rates | 4.8 kbaud, 38.4 kbaud and 230.4 kbaud |
| Cable length | max. 20 m |
| Power supply | via E-bus and power contacts |
| Electrical isolation | 500 V (E-bus/signal voltage) |
| Power contacts | yes |
| Supply current for devices | < 200 mA per device (method 1) |
| Current consumption E-bus | typ. 120 mA |
| Special features | each channel parameterisable in TwinCAT |
| Weight | approx. 60 g |
| Operating/storage temperature | 0…+55 °C/-25…+85 °C |
| Relative humidity | 95 %, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27/29 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. class/installation pos. | IP 20/variable |
| Approvals | CE, UL, Ex |
![]() |
![]() |
| Related products | |
|---|---|
| EP6224-0002 | EtherCAT Box, 4-channel IO-Link master |
![]() |
![]() |
| System | |
|---|---|
| subsystem | For further subsystem products please see the system overview. |
![]() |
![]() |